SolarMax S series

  SolarMax 2000S SolarMax 3000S SolarMax 4200S SolarMax 6000S
Input values
MPP voltage range 100 V…550 V 100 V…550 V 100 V…550 V 100 V…550 V
Minimum voltage for rated power 190 V 260 V 200 V 240 V
Maximum DC voltage 600 V 600 V 600 V 600 V
Maximum DC current 11 A 11 A 22 A 22 A
Connection type MC4 MC4 MC4 MC4
Output values
Rated output power at cos(φ) = 1 1’980 W 2’750 W 4’180 W 5’060 W
Maximum apparent output power 1’980 VA 2’750 VA 4’180 VA 5’060 VA
Nominal mains voltage / range 230 V / 184 V...300 V 230 V / 184 V...300 V 230 V / 184 V...300 V 230 V / 184 V...300 V
Maximum AC current 12 A 12 A 19 A 22 A
Mains nominal frequency / range 50 Hz / 45 Hz…55 Hz
Power factor cos(φ) Adjustable from 0.8 overexcited to 0.8 underexcited
Distortion factor at rated power < 1.5 %
Connection type Wieland
Grid connection One-phase (1 / N / PE)
Efficiency
Max. efficiency 97 % 97 % 97 % 97 %
Europ. efficiency

95.4 %

95.5 % 95.8 % 96.2 %
Power input
Own consumption (night) 0 W
Ambient conditions
Protection type compliant with EN 60529 IP54
Ambient temperature range -20 °C…+60 °C
Ambient temperature range at rated power -20 °C…+45 °C
Relative humidity 0…98% (no condensation)
Configuration
Display Graphic LC display with backlight and status LED
Circuit type Two-stage, transformerless (no galvanic isolation)
Data logger Data logger for energy yield, peak output and operating duration for the last 31 days, 12 months and 10 years
Fault current monitoring Internal, AC/DC sensitive
Casing Aluminium, cover powder-coated
Overvoltage conductor DC Requirement class D (VDE 0675-6) or type 3 (EN 61643-11)
Overvoltage conductor AC Requirement class D (VDE 0675-6) or type 3 (EN 61643-11)
Standards & guidelines
CE-compliant Yes
EMC EN 61000-6-2 / EN 61000-6-3 / EN 61000-3-2 / EN 61000-3-3 / EN 61000-3-11 / EN 61000-3-12
Standard/guideline compliance VDE-AR-N 4105 / VDE 0126-1-1 / CEI 0-21 / DK 5940 Ed. 2.2 / RD 661 /
RD 1699 / G83/1-1 / G83/2 1) / G59/2 2) / PPC Guide / C10/11 / EN 50438 3) / AS4777
Device safety “GS certified safety” VDE / AS3100
Interfaces
Data communication RS485 / Ethernet via two RJ45 sockets
Status signalling contact M12 connector with relay as N/C contact / N/O contact
Weight & dimensions
Weight 13 kg 13 kg 15 kg 15 kg
Dimensions in mm (W x H x D) 545 x 290 x 185 545 x 290 x 185 545 x 290 x 185 545 x 290 x 185
Warranty
Warranty Standard 5 years / extension to 10, 15, 20 or 25 years possible

1) in development
2) Only the inverters SolarMax 4200S and SolarMax 6000S
3) Portugal

All rights, amendments and errors reserved.

SolarMax 6000S efficiency curve