SolarMax TS-SV series

  SolarMax 330 / 660 / 990 / 1320 TS-SV SolarMax 360 / 720 / 1080 / 1440 TS-SV
Input values
MPP voltage range 450...800 V 510…800 V
Maximum DC voltage 900 V 900 V
Maximum DC current 720 / 1440 / 2160 / 2880 A 720 / 1440 / 2160 / 2880 A
Number of MPP-Trackers 1 or 3 / 6 / 9 / 12 1 or 3 / 6 / 9 / 12
Connection type threaded bolts M8
Overvoltage Category 2
Output values
Rated output power 330 / 660 / 990 / 1320 kW 1) 360 / 720 / 1080 / 1440 kW 2)
Maximum apparent output power 340 / 680 / 1020 / 1360 kVA 370 / 740 / 1110 / 1480 kVA
Nominal mains voltage 3 x 280 V 3 x 320 V
Maximum AC current 700 / 1400 / 2100 / 2800 A 666 / 1332 / 1998 / 2664 A
Mains nominal frequency / range 50 Hz / 45 Hz…55 Hz (60 Hz / 55 Hz...65 Hz upon request)
Power factor cos(φ) Adjustable from 0.8 overexcited to 0.8 underexcited
Distortion factor at rated power < 3 %
Connection type 3 x 3 threaded bolts M8
Grid connection Three-phase (without a neutral conductor)
Overvoltage Category 2
Efficiency
Maximum efficiency 98 % 98 %
Europ. Efficiency 3) 97.2 %
97.4 %
Power input
Own consumption, night < 7 / 14 / 21 / 28 W
Ambient conditions
Protection type compliant with EN 60529 IP20
Ambient temperature range -20 °C…+50 °C
Ambient temperature range at rated power -20 °C…+45 °C
Relative humidity 0…98% (no condensation)
Maximum altitude above sea level 2000m (without derating) 
Noise emissions < 65 dBA (↔ 1.5 m)
Degree of soiling PD2
Configuration
Display (in MCU) Graphic LC display with backlight and status LED
Data logger (in MCU) Data logger for energy yield, peak output and operating duration for the last 31 days, 12 months and 10 years
Galvanic insulation No galvanic isolation: direct connection to MV transformer
Standards & guidelines
CE-compliant Yes
EMC EN 61000-6-2 / EN 61000-6-4
Standard / guideline compliance G59/2 / BDEW MV Guideline/ PPC Guide / RD 661
Device safety IEC/EN 62109-1
Interfaces
Data communication (in MCU) RS485 / Ethernet via two RJ45 sockets
Status signalling contact (in MCU) Potential-free terminal contact pair (configurable function)
Alarm input (in MCU) Terminal contact pair for connection to MaxConnect plus
Inverter shut-off 1 Two terminal contact pairs (can be chain-linked via several SolarMax TS-SV)
Inverter shut-off 2 (in MCU) Terminal contact pair
Weight & dimensions
Weight 990 / 1980 / 2970 / 3960 kg
Dimensions in mm (W x H x D) 1 / 2 / 3 / 4 x 1200 x 1970 x 800 mm
Warranty
Standard warranty 2 years (free extension to 5 years after registration)
Warranty extensions to 10, 15, 20, or 25 years

1) at cos(φ) = 1, UAC = 280 V
2) at cos(φ) = 1, UAC = 320 V
3) in single MPPT operation
with active partial load optimisation
(see operating instructions parameter
configuration with MaxTalk 2 Pro)

All rights, amendments and errors reserved.

Efficiency SolarMax TS-SV 3)